HIGH TECH MEDICAL WEST INCINERATOR

Q: what is kind of waste can use in this equipment?

A: This equipment for medical waste, pet animal, Municipal waste, live waste. Prohibit any explosive and radiation material, liquid waste and gas waste.

 

Q: Incinerator Smoke Standard

A: China Government Standard: No.GB18484-2001.

 

Q: Treatment capacity

A: Average Capacity calculated by medical waste(lower calorific power (L.C.P): 3.0TH Kcal/Kg per hour), not mean any waste material. The animal/pet combustion rate around 2/3 of average capacity. 

 

Clover incinerator use time per day up to 24 hours. Between each feed/combustion time, there are about 0.5-1 hours cooling time and time for feeding waste. Actual combustion time per day is around 16 hours. The lifetime of incinerator between 5-10 year according to use.

 

Generally, we proposal small laboratory, small clinic use capacity under 20 kgs per hour. When incinerator use in hospital, please calculate the waste output capacity around 2kgs per people per day. If there are 200 sickbed in the hospital, that’s mean you need one incinerator capacity around 400kgs per day, change to capacity per hour is around 30-40 kgs per hour. According the operation time per day, waste material, budget, development, etc, you can use capacity from 30-50 kgs per hour incinerator.

 

Model

YD-100

Picture

 

Burning Rate

Average 100 kgs/hour

Feed Capacity

Average 200 kgs

Primary Combustion Chamber

1200 Liters

Secondary Combustion Chamber

500 Liters

Mix Combustion Chamber

Yes

Smoke Filter Chamber

Yes

Feed Mode

Manual

Voltage

220V

Power

0.9Kw

Fuel Type

Diesel Oil/ Natural Gas/LPG

Burner

Italy Original

Oil Consumption (Diesel Oil)

14--28 kg/hour

Gas Consumption (Natural Gas)

10--32.2 m3/hour

Internal Dimensions

130 x 100 x 90cm (primary chamber)

External Dimensions

220 x 180 x 360cm (without chimney)

Temperature Monitor

Yes

Oil Tank Capacity(if oil fuel)

300 Liters

Door Opening

55 x 80cm

Chimney Length

10.0 Meters

Chimney Type

Stainless Steel

Equipment Gross Weight

6300 kgs

Operation Technical Specifications

Primary Chamber Temperature

800-1000

Secondary Chamber Temperature

1000-1200

Residency Time

2.0 Sec.

Burning Efficiency

98%

Waste Lower Calorific Power

3000Kcal

 
Thermocouple.
Temperature gauge.
Fire rope.
Burner.
Induction air fan.
Digital temperature display panel
incinerator for medical and animal waste (diesel, up to 50 kg)
Preamble Incinerator (hospital waste management system) is a turn-key project which will comprise a hospital grade incinerator, allied accessories and operation for proper disposal of hospital General medical waste (plastics, gloves and papers) and Infectious waste (blood-soaked bandages, sharps waste, surgical waste, human or body parts, cultures, and swabs).the unit should be of high performance to operated continuously for at-least 12 hours daily. Energy/Fuel Source for incinerator will be Natural Gas based on Pyrolysis with smokeless emission, for ensuring the clean environment system should strictly comply with Environmental Protection Agency (EPA) Pakistan emission standards.  
For medical and animal waste
Maximum load up to 50 kg.
Weight is not more than 400 kg.
The presence of a refractory layer
Burning time at full load /2-3 hours.
Diesel burner (maximum burning): 5.11 l/h. 
Power supply – 220V/50Hz.
Combustion temperature – norm 760 Co, increase to 870 is allowed.
*Specifications OF Incinerator (hospital waste management system): 
1. Burning Capacity
i. Incinerator should be capable to burn waste @ 100 kg / hr in single loading.
2. Construction:
i. Packaged type skid mounted dual chamber construction